Chapter 4 ________________________________________________________________ Operation
VAISALA ______________________________________________________________________ 121
Mode 4 is usually used if an alarm needs to be triggered when the
measured value exceeds a safe range. The relay is active when
measurement is in range, and is released if the value goes out of range or
the measurement fails.
NOTE
If the measurement of the selected quantity fails or the transmitter loses
its power, the relay is released.
Hysteresis
Hysteresis function is to prevent the relay switching back and forth when
measured value is near to the setpoint values.
Relay is activated when the measured value passes the exact value of the
setpoint. When returning and passing the setpoint again relay is released
only until the value reaches the setpoint increased/decreased by the
hysteresis value.
Hysteresis should be smaller than difference of the setpoints.
Example: When the 'active above' value is -30 ºC and the hysteresis value
is 2 ºC, relay activates when the dewpoint reaches -30 ºC. As the
dewpoint then decreases, relay releases at -32 ºC.
>rsel tdf t
Rel1 Tdf above: - ? -30
Rel1 Tdf below: -30.00 'C ? -
Rel1 Tdf hyst : 5.00 'C ? 2
Rel1 Tdf enabl: ON ?
Rel2 T above: 30.00 'C ?
Rel2 T below: 20.00 'C ?
Rel2 T hyst : 1.00 'C ?
Rel2 T enabl: ON ?
>
NOTE
If both setpoints are specified and "above" setpoint is lower than
"below" setpoint, the hysteresis works in the opposite direction, that is,
relay is released when the measured value passes the exact value of the
setpoint.