Vaisala HUMICAP MMT162 Guia do Utilizador Página 47

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 46
Chapter 4 _________________________________________________________________ Operation
VAISALA ________________________________________________________________________ 45
Configuration Commands Related to Modbus
In addition to enabling the Modbus protocol in the device, Modbus over
RS-485 needs the following software settings: serial bit rate, parity,
number of stop bits, and Modbus device address.Use the service
commands listed in Table 10 below to configure the Modbus RTU using
the USB service cable.
Table 10 Configuration Commands for Modbus RTU
Service Command
Description
SMODE MODBUS
Enable Modbus communication protocol
SERI b p 8 s
Change baud rate and parity
b = baud rate (9600, 19200, 38400, 57600, 115200)
p = parity (E, N, or O)
8 = number of data bits must be 8
s = number of stop bits (2 if parity is N, 1 otherwise*)
Bit rates less than 9600 b/s are not supported with
Modbus.
ADDR a
Set Modbus address
a = new address (0…255)**
SDELAY d
Add extra Modbus response delay***
d = new delay in units of 1/250 seconds (0…255)
* Modbus specification defines that two stop bits must be used if parity is N.
** Setting address to zero switches the instrument offline from the Modbus bus.
Addresses 248 … 255 are not supported by the Modbus standard but MMT162 works
with them.
*** Extra response delay can be used, for example, to avoid problems caused by
direction-switching delays in bus converters.
NOTE
The instrument must be switched off and on before the configuration
changes made with the service cabl
e take effect.
Vista de página 46
1 2 ... 42 43 44 45 46 47 48 49 50 51 52 ... 74 75

Comentários a estes Manuais

Sem comentários