HUMIDITY
558
HUMIDITY
9
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
kele.com888-397-5353 USA
March 2014
Humidify / Fan Dehumidify / Fan
24 VAC/VDC
GND 10kΩ Type II thermistor
Terminal-description:
1. Connection for power-supply (24 VAC/VDC, ±10%). In case of DC,
connect the negative power-terminal. Common connection for analog
inputs and outputs.
2. Connection for power-supply (24 VAC/VDC, ±10%). In case of DC,
connect the positive power-terminal.
3. Contact “DO 1” Humidify or Fan, 2A maximum
4. Contact “DO 1” Humidify or Fan, 2A maximum
5. Contact “DO 2” Dehumidify or Fan, 2A maximum
6. Contact “DO 2” Dehumidify or Fan, 2A maximum
7. Thermistor input “RT” (10k
Ω
Type II thermistor)
8. Thermistor input “RT” (10k
Ω Type II thermistor)
TDC-BH-U
Accuracy ±5% RH (10-90%)
Supply Voltage 24 VAC ±10%, 50-60 Hz 1.5 VA,
24 VDC, 63 mA
Anolog Input 10K Type II (Type 24) thermistor
Relay Output 2 NO SPST Relays, 2 Amps @ 24
VAC
Operating Humidity 0% to 95% non-condensing
Operating Temperature 32° to 122°F (0° to 50°C)
Enclosure Rating Polycarbonate PC (UL class V-0)
Wiring Terminations Terminal block (12 to 24 AWG
Approvals CE
Weight 0.48 lb (0.22 kg)
Warranty 2 years
DESCRIPTION
The Vector Model TDC-BH-U Duct Mount Humidistat is a
stand-alone programmable electronic humidistat designed
for controlling humidification and dehumidification equipment
in HVAC and energy management systems. The TDC-BH-U
Series features one internal humidity sensor, one external
temperature sensor input and two relay outputs. Humidity
reset is possible using the ST-O24 outdoor air temperature
sensor for cold weather applications to prevent condensation.
The TDC-BH-U-D Series comes with all of the features
of the base model plus a time clock feature for advanced
programming with 48 hour backup.
FEATURES
• Humidification and Dehumidification control
• External temperature input for set point setback
• Programmable user interface
• Optional time clock
• 2 relay outputs
• Easy to read display
• Replaceable sensor
CONNECTION TERMINALS
SPECIFICATIONS
5% DUCT MOUNT HUMIDSTAT
TDC SERIES
Comentários a estes Manuais