Vaisala HUMICAP HMW90 SERIES Especificações Página 23

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 74
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 22
517
HUMIDITY
HUMIDITY
9
WE MAKE IT EASY.
kele.com 888-397-5353 USA
March 2014
2% DUCT AND OSA HUMIDITY TRANSMITTERS
HMD60, HMD70, AND HMK41K
HMD60, HMD70
Accuracy
Humidity ±2% RH (0% to 90% RH) @68°F
(20°C)
Temperature ±0.2°C
Supply Voltage
60 Series 10 to 35 VDC
70 Series 10 to 35 VDC, 9 to 24 VAC @ 0.3 VA
(signal dependant)
Maximum Output
Impedance 500Ω @ 24 VDC
Minimum Output
Impedance 3000Ω min
Measurement Range
Humidity
Duct Mount 0% to 100%
Temperature
Duct Mount -4° to 176°F (-20° to 80°C)
Sensing Technology Capacative and replaceable, Vaisala
HUMICAP
®
180
Operating Temperature
Electronics 23° to 131°F (-5° to 55°C)
Sensor Head (Duct) -4° to 176°F (-20° to 80°C),
Enclosure Rating Cast aluminum NEMA 4 (IP55),
ABS plastic
Wiring Terminations Screw terminals (20-16 AWG)
Approvals CE
Weight
Duct 1.68 lb (0.76 kg)
Warranty 1 year
HM41K
Sensor Capacitive and replaceable
Operation Handheld, onsite calibrator
Reference Probe
Accuracy ±1% RH (0% to 90% RH)
±2% RH (90% to 100% RH)
Measuring range 0% to 100% RH,
-40° to 140°F (-22° to 78°C)
Operating temperature -40° to 140°F (-40° to 60°C)
Storage temperature -4° to 140°F (-20° to 60°C)
Temperature coefficient
+0.04% RH/°C typical
Agency approvals CE, NIST certificate
Weight 2.1 lb (0.95 kg)
Warranty 1 year
DESCRIPTION
Vaisala’s Models HMD60 and HMD70 Duct Mount Relative
Humidity Transmitters have been specifically designed
for use in HVAC/BAS and pharmaceutical applications.
These instruments measure relative humidity from 0% to
100%. They are easily installed and meet the European CE
standards.
Five-minute field calibration is possible using the Model
HMK41K Humidity Calibrator. When accuracy adjustment
or sensor replacement is necessary, the transmitter can be
calibrated in seconds with a single potentiometer without
disturbing operation. This saves hours of maintenance time
and assures high accuracy.
FEATURES
Comes with NIST certificate
Full 0% to 100% RH measurement
State-of-the-art replaceable sensor technology
SPECIFICATIONS
HMD 60
or
HMD 70
Vista de página 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 73 74

Comentários a estes Manuais

Sem comentários