
507
HUMIDITY
HUMIDITY
9
WE MAKE IT EASY.
kele.com 888-397-5353 USA
March 2014
Duct
Housing
(D)
Room
Housing
(S)
OSA / Wall
Housing
(O)
1% AND 2% WALL, DUCT AND OSA HUMIDITY TRANSMITTERS
HT829, HT839
Accuracy
1% units ±1% from 10% to 80% RH
2% units ±2% from 0% to 90% RH
Time Constant 60 sec in slow-moving air
Supply Voltage 9.4 VDC min to 35 VDC max
Signal Output Two-wire, 4-20 mA over 0% to 100%
RH and temperature (HT839)
Maximum Output
Impedance 730Ω @ 24 VDC (Power supply - 9.4)
/ 0.02 A = Ω
Sensing Technology Capacitive monolithic IC (Humidity)
Sensor Protection Sintered filter (Humidity)
Calibration One-point adjustment
Adjustments Zero, noninteracting
Operating Temperature
Room -10° to 150°F (-23° to 66°C)
Duct/OSA -10° to 185°F (-23° to 85°C),
Wiring Terminations Nonpolar terminals, connect either
way (22-14 AWG wire)
Dimensions
Room 4.5"H x 2.8"W x 1.5"D
(11 x 7 x 4 cm)
Duct 4.6"L x 2.9"W x 2.3"D
(22 x 7.3 x 5.7 cm), 4.6" (11.8 cm)
probe length 0.38" (0.95 cm) Ø
OSA 10.2"L x 2.7"W x 2.3"D
(26x 7 x 5.7 cm), 8" (20 cm) probe
length 1.25" (3.2 cm) Ø
Weight
Room 0.3 lb (0.13 kg)
Duct 1.1 lb (0.5 kg)
OSA 1.16 lb (0.53 kg)
Warranty 3 years
DESCRIPTION
The Minco Model HT829 Relative Humidity Transmitter
measures 0% to 100% RH over a range of -10° to 185°F
(-23° to 85°C). The standard two-wire, 4-20 mA output
provides low-cost space, duct, and outdoor monitoring
or process and industrial building control. A temperature
sensor built into the integrated circuit provides temperature
compensation over the full temperature range.The HT839
Series has temperature transmitter output.
FEATURES
• Temperature-compensated IC sensor
• One-point field calibration, RH or temperature
• Weatherproof housing for OSA and duct
• 1% or 2% RH accuracy
• Sintered filter
24VDC
RH
4-20mA
Signal
SZ
*Non-polar connections
Hum*
Hum
+
-
+
–
24VDC
RH Signal
4-20mA
**Temp Signal
4-20mA
S
H
Hum*
Hum
Temp*
Temp
* Non-polar connections
** Need humidity connection
to output temperature
signal properly
T
Z SZ
+
-
–
+
–
+
WIRING — HT829, RH ONLY WIRING — HT839, RH AND TEMPERATURE
SPECIFICATIONS
FM
Comentários a estes Manuais