HUMIDITY
530
HUMIDITY
9
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
kele.com888-397-5353 USA
March 2014
3% WALL, DUCT AND OSA HUMIDITY TRANSMITTERS
H_30K SERIES
Accuracy 3% RH @ 73°F (23°C) from 5% to
90%; (0-5% & 90%-100%) add 4%
Stability typically <0.5% drift per year
Thermal Effect 0.05% per °F
Supply Voltage 9.5-28 VDC
Signal Output RH: 4-20 mA
Temperature: 4-20 mA, optional
thermistor, RTD
Maximum Output
Impedance 725 @ 24VDC (Supply voltage -
9.5V) / 0.02)
Measurement Range
RH 0-100%
Temperature -20° to 140°F (-29° to 60°C)
(see ordering information)
Sensor Protection Sintered filter (duct and OSA)
Operating Humidity 0-100% RH non-condensing
Operating Temperature -20° to 158°F (-29° to 70°C)
Enclosure Beige plastic (room), weather
resistant cast aluminum (duct and
OSA)
Wiring Terminations Terminal block (22 to 16 AWG)
Weight
Wall 0.3 lb (0.09 kg)
Duct 1.14 lb (0.52 kg)
OSA 1.2 lb (0.54 kg)
Approvals RoHs
Warranty 18 months
DESCRIPTION
The Kele Series H_30K Humidity Transmitters have been
specifically designed for use with HVAC/BAS applications.
These instruments measure relative humidity from 5 to 90%
with 3% accuracy and produce a two wire, 4-20mA linear
output. All can come equipped with an optional passive RTD
or thermistor. The duct and OSA versions may also be fitted
with a 4-20mA temperature transmitter.
FEATURES
3% accuracy (5% to 90%)
Two wire, 4-20mA RH output
Optional temperature thermistor
Optional temperature RTD
Optional temperature 4-20mA (Duct or OSA)
OPERATION
The temperature compensated circuitry converts the relative
humidity into a 4-20 mA signal. The optional temperature
sensors, RTDs or thermistors, offer direct connection to most
automation systems. On duct and OSA units, an optional 4-20
mA temperature transmitter may also be employed and is
rangeable from -30° to 250°F (-34° to 121°C).
DIMENSIONS
SPECIFICATIONS
Foam gasket
5.25
(13.3)
4.43
(11.3)
2.88
(7.30)
2.125
(5.4)
1.25
(3.18)
HO30K
2.875
(7.3)
4.625
(11.7)
2.13
(5.4)
7.0
(17.8)
0.25
(0.64)
4.50
(11.43)
3.23
(8.20)
in
(cm)
HW30K
HD30K
HO30K
HD30K
HW30K