5.4.1.2 Selecting and scaling the analogue output quantities
Disconnect the security lock jumper!
ASEL xxx yyy <cr>
xxx = channel 1's quantity
yyy = channel 2's quantity (RH, T, Td, dT, Abs, Mix or Tw)
Example: RH selected on channel 1 and temperature on channel 2
>ASEL RH T <cr>
Ch1 (RH) lo 0.000 %RH? <cr>
Ch1 (RH) hi 100.000 %RH ? <cr>
Ch2 (T ) lo -40.000 'C ? <cr>
Ch2 (T ) hi +160.000 'C ? <cr>
5.4.1.3 Scaling the analogue outputs
Disconnect the security lock jumper!
ASCL <cr>
Example: relative humidity is scaled in the range 0...100 %RH and tem-
perature in the range -40...+160 °C
>ASCL <cr>
Ch1 (RH) lo 0.000 %RH? <cr>
Ch1 (RH) hi 100.000 %RH ? <cr>
Ch2 (T ) lo 0.000 'C ? -40 <cr>
Ch2 (T ) hi 100.000 'C ? 160 <cr>
5.4.2 Output via the serial bus
5.4.2.1 Starting the measurement output
R <cr>
Starts output of measurements to the peripheral devices (RUN mode); the only
command that can be used is S (stop). The output mode can be changed with
command FORM (see Appendix 1).
5.4.2.2 Stopping the measurement output
S<cr>
Ends the RUN mode; after this command all other commands are available.